Texas Demand Charges: How They Work and How to Reduce Them

A plain-English guide for Texas facility managers, CFOs and operations teams. How utilities bill your peak, why one 15-minute spike can follow you for a year, and what actually brings that number down.

What is a demand charge?

A demand charge is the part of a commercial electric bill based on your facility’s highest rate of power use, measured in kilowatts (kW), instead of the total energy you used, measured in kilowatt-hours (kWh). In most of Texas, the utility looks at every 15-minute interval in the billing month and bills you on the single highest one.

That means a facility can run efficiently for 2,975 intervals a month and still pay for the one interval when the chillers, compressors and production line all came on together. Depending on your utility, that peak can also set a minimum you pay for the next 11 months.

How demand charges are calculated

Your bill has two very different meters running at once:

  • Energy (kWh): how much electricity you used over the month. Think of it as miles driven.
  • Demand (kW): how fast you used it at your busiest moment. Think of it as your top speed. Utilities size wires, transformers and substations for that top speed, and demand charges are how they recover that cost.
  • The interval: demand is usually averaged over 15 minutes. A motor’s start-up surge that lasts seconds matters less than several large loads running together for a quarter hour.
  • The threshold: most Texas utilities start billing commercial demand once a site goes above about 10 kW. Above that line, a large share of the delivery bill shifts from per-kWh to per-kW.

A simple example

An illustrative 400 kW facility at roughly $12 per kW of billed demand:

Scenario Billed demand Monthly demand cost
Normal monthly peak 400 kW $4,800
Same month, one 15-minute spike 480 kW $5,760
Following winter month, actual peak 350 kW, 80% ratchet in effect 384 kW (80% of 480) $4,608 instead of $4,200

Simplified illustration, not a quote. Actual rates, ratchet rules and rate classes vary by utility, meter type and tariff. An accurate picture requires your own 15-minute interval data.

Three ways your peak shows up on the bill

Texas commercial bills can charge for peak demand in up to three different ways. Which ones apply depends on where your facility is and what kind of meter it has.

  • Your own monthly peak. The highest 15-minute interval in the billing month, billed per kW. This applies almost everywhere.
  • A ratchet. Some utilities bill the higher of this month’s peak or a percentage of a past peak. With an 80% ratchet, one bad July afternoon can set a floor for the next 11 months.
  • Coincident peak (4CP) transmission charges. Many larger, interval-metered sites pay transmission costs based on their demand during the four 15-minute intervals when the whole ERCOT (Electric Reliability Council of Texas) grid peaked, one each in June, July, August and September. That number then sets a charge for the following year.

How Texas utilities bill demand

Texas doesn’t have one demand charge. It has several, depending on whether you’re in a competitive retail area, a city-owned utility, or an electric cooperative. Here’s the short version.

Utility area How the peak is measured Carryover / ratchet Transmission piece
Oncor (DFW and much of North and Central Texas) Highest 15-minute interval each month Higher of the monthly peak or 80% of the highest peak in the prior 11 months 4CP for interval-metered (IDR) sites; monthly peak for others
CenterPoint (Houston area) Highest 15-minute interval each month, in kVA 80% ratchet on the prior 11 months for most loads 4CP for IDR sites; monthly peak for others
AEP Texas (Corpus Christi, Rio Grande Valley, West Texas) Highest 15-minute interval each month 80% ratchet on the prior 11 months 4CP for IDR sites
Austin Energy Highest 15-minute interval each month No ratchet found in the current tariff; summer demand sets your rate class for the next year Regulatory Charge billed on your monthly peak
CPS Energy (San Antonio) Highest 15-minute interval each month October–May billing demand is at least 80% of your previous June–September peak Included in CPS rates
Pedernales Electric Cooperative (Hill Country) Highest 15-minute interval each month (Large Power, 50 kW+) None noted Billed on your 4CP demand from the previous summer

Based on published tariffs and rate pages reviewed November 2026. Utilities update these schedules regularly, and exceptions apply by rate class and meter type. Check your own bill and tariff, or ask us to review them with you.

Oncor, CenterPoint and AEP Texas: competitive retail areas

In DFW, Houston and other competitive areas, your bill combines two businesses. Your retail electric provider sells you energy. The wires utility (Oncor, CenterPoint or AEP Texas) delivers it, and its delivery charges are where most demand charges live.

Published delivery charges for large secondary-voltage commercial service have run roughly $10 to $13 per kW per month in late 2025 and 2026, before the energy you buy. The 80% ratchet is the detail that surprises people most. A single high month keeps raising your bill long after it’s over.

Choosing your retail energy provider: your provider can’t change the wires utility’s demand rates, but contracts differ in how they pass those charges through. Some show them as separate line items; others bundle them. It’s worth knowing which you have before you compare offers or model savings.

Austin Energy, CPS Energy and co-ops

Austin Energy bills demand on your highest 15-minute interval every month, and we haven’t found a ratchet in its current tariff. Summer still matters: your average June through September demand decides which rate class you’re in the following year. With the Regulatory Charge included, each kW of monthly peak now costs about $15.35 for 10–300 kW secondary customers and $18.22 for 300 kW and up. More on the Austin and Hill Country page.

CPS Energy charges more per kW in summer, and its summer peak carries forward. From October through May, billing demand is the greater of that month’s peak or 80% of your highest June–September peak.

Pedernales Electric Cooperative Large Power members pay a Peak Capacity Charge on their highest 15-minute interval plus a transmission charge based on their 4CP demand from the previous summer. Other co-ops use their own rules.

How to reduce demand charges

There’s no single fix. The right mix depends on when your peaks happen, what causes them and which billing rules apply. In practice, demand charge mitigation draws on five tools:

  • Load management. Stagger start-ups, sequence HVAC and process loads, and use controls to stop big loads from stacking up in the same 15 minutes. Often the cheapest place to start.
  • Commercial solar. Lowers the energy you buy and can trim daytime peaks on sunny afternoons. It isn’t reliable for the demand charge on its own (more below).
  • Battery energy storage (BESS). A battery energy storage system can discharge during your peak intervals and hold grid draw below a target, known as peak shaving. Covering a 15- to 30-minute spike is short work for a properly sized battery. The harder part is controls that know when the peak is coming. More on commercial battery storage.
  • On-site generators. Some facilities run natural gas or diesel generators during peak intervals or likely 4CP windows to cut grid demand. It can work, but there are real tradeoffs: fuel, maintenance, runtime limits, noise and emissions. The backup generator most facilities already have usually can’t be used this way. Federal rules for emergency engines bar using them for peak shaving, so a generator used to manage demand typically needs a non-emergency permit and has to meet stricter emissions standards. Battery storage does the same peak-shaving job with no fuel or air permit, and it can be paired with a generator for longer outages.
  • Coincident peak response. For sites billed on 4CP, cutting load or discharging storage during likely ERCOT summer peaks may reduce next year’s transmission charges.

Can solar alone eliminate demand charges?

Usually not, and you should be wary of anyone who says otherwise. Your billed peak only has to happen once. A passing cloud at 2:00 p.m., or a peak at 5:30 p.m. when panels are winding down, and the demand charge is set for the month regardless of how well solar did the rest of the time.

Solar still earns its keep by cutting the energy you buy, which is often the larger part of the bill. Pairing it with storage and controls is what makes the demand side more predictable.

What a battery can and can’t do

A battery can only shave a peak it has the charge, power rating and warning to cover. If it’s depleted, undersized, or the controls miss the interval, that interval still sets the bill. That’s why sizing starts with your interval data, not a rule of thumb.

Results vary by load profile, tariff and system design. Storage may reduce demand charges and exposure to price spikes, but it isn’t a guarantee or a profit engine.

Changes Texas businesses should watch

  • ERCOT 4CP may become 12CP. In July 2026 the Public Utility Commission of Texas proposed replacing the four summer coincident peaks with twelve, one per month, measured over 30-minute intervals (Project No. 58000). It isn’t final. If adopted, winter mornings and evenings, when solar produces little, would start to count.
  • Peaks are moving later. ERCOT’s annual peak used to land around 5:00 p.m. It has drifted toward 6:00–7:00 p.m., past solar’s best hours. That shifts more of the job to storage and load control.
  • Austin Energy pays for summer load reduction. Its Commercial Demand Response program pays businesses for cutting load during summer peak events. Whether battery discharge qualifies isn’t spelled out publicly, so check with us before counting on it. Other incentives are on our battery incentive programs page.

How NATiVE Solar approaches demand charges

NATiVE Solar has designed and built commercial systems in Texas since 2007. We treat demand charges as an engineering problem, not a sales pitch.

  • Start with your data. We review 12 months of bills and 15-minute interval data. In competitive areas that data is usually available through Smart Meter Texas; Austin Energy and CPS Energy provide it through their business portals.
  • Find what sets the peak. Which equipment, which months, which hours, and which billing rules (monthly, ratchet or 4CP) are driving the cost.
  • Model the options honestly. Load management, solar, storage, or a combination, including what each one can’t do for your site.
  • Design, build and support it. Engineering, permitting, interconnection, installation and long-term O&M from one Texas team.

For the bigger picture on system design, tax credits and delivery, see commercial solar and battery storage in Texas.

Demand charge FAQ

It’s a charge based on your highest rate of power use (kW) during the billing period, usually the highest 15-minute interval, rather than total energy used (kWh). Utilities use it to recover the cost of the capacity needed to serve your peak.

Most Texas utilities average your power use over 15-minute intervals and bill the highest one in the month. CenterPoint measures in kVA rather than kW. Larger interval-metered sites in competitive areas may also pay transmission costs based on their demand during ERCOT’s four summer coincident peaks (4CP).

A ratchet sets a minimum billed demand based on a past peak. Under Oncor, CenterPoint and AEP Texas tariffs, billed demand for most large commercial customers is the higher of the current month’s peak or 80% of the highest peak in the previous 11 months. CPS Energy carries 80% of your summer peak into October through May.

Not the wires utility’s demand rates. Those are set by tariff and are the same no matter which provider you choose. Providers differ in energy pricing and in how they pass delivery charges through, so it’s worth reading the contract closely.

Usually not on their own. Your billed peak only has to happen once, and clouds or late-afternoon peaks can set it while solar output is low. Solar mainly reduces the energy you buy; storage and load control make the demand side more predictable.

A battery discharges during peak intervals to keep grid draw below a target, which is called peak shaving. Results depend on battery size, controls and your load profile. It may reduce demand charges, but no system can guarantee a specific outcome.

Usually not without changes. Most standby generators are permitted as emergency engines, and federal rules don’t allow those to be used for peak shaving or non-emergency demand response. Facilities that use generators to manage demand typically need engines permitted for non-emergency use. Check with your environmental consultant before running a generator for anything other than emergencies and testing.

4CP refers to the four 15-minute intervals when the ERCOT grid peaks each summer, one each in June through September. Many large sites pay transmission costs based on their demand in those intervals. In July 2026 the PUC proposed moving to a 12CP method with 30-minute intervals. That proposal isn’t final.

Ideally 12 months of utility bills and 15-minute interval data, plus a sense of your major equipment and operating hours. We’ll help you pull the data if you haven’t before.

Find out what is setting your peak